CH boilers service – problems and solutions

Correct operation of CH boilers translates into their trouble-free use and contributes to long service life of the equipment. Below is a table showing the most common causes of failure of heating boilers and ways to avoid these defects.

If you experience a CH boiler defect, we encourage you to get in touch with Kamen’s technical support.

Boiler problems and remedies.

PROBLEMPOSSIBLE CAUSEREMEDY
The required temperature is not reachedLow calorific value of fuelUse fuel with the required parameters
Excessive flue draftThrottle the draft with a damper in the smoke conduit
Wrong settings of combustion parametersAdjust the settings of the electronic controller
System incorrectly madeCheck the central heating system
Incorrectly selected boiler for the building
Contaminated exchangerClear the boiler
Temperature sensor damagedReplace the temperature sensor
Smoke escapes from the doorIncorrectly closed doorAdjust the door lock and hinge
Cord contaminationClean the cord
Packing cord damagedReplace the packing cord
Too low chimneyExtend the chimney
Too low chimney cross sectionIncrease the chimney cross section
Plugged chimneyClean the chimney
Contaminated boilerClear the boiler
Too high fan speedReduce fan speed
Very low atmospheric pressure
Sudden increase in pressure and temperatureClosed valvesOpen the valves
Frozen expansion vesselInsulate the expansion vessel
The fan does not turn off when the set temperature has been reachedReset the controller and restart it. If it still does not shut down, request controller maintenance
Much higher boiler water temperature than the set temperatureExcessive flue draft with excessive calorific value of fuelUse a chimney draft controller or fuel with required parameters
Short gas burstsToo low boiler temperature settingIncrease the temperature
No heat uptake from the boilerDo not close all radiators with valves
No heat uptake from the boilerAllow heat uptake by the radiators and other receivers, such as the boiler
Wrong settings of combustion parametersAdjust the settings of the electronic controller
Air swirling in the chimneyInstall a chimney cap
Strong overheating of the chimneyExcessive flue draftMeasure the flue draft and, if necessary, throttle it
Excessive flue draftMeasure the flue gas temperature, correct temperature is within 110°-230°C
Incorrect position of the boiler versus the chimneyFollow the recommendations of the operating instructions
Excessive fuel consumptionCH system incorrectly madeCheck the central heating system
Incorrectly selected boiler for the building
Too low calorific value of fuelUse fuel with the required parameters
Wrong settings of combustion parametersAdjust the settings of the electronic controller
Low boiler efficiency due to high chimney lossExcessive smoke conduit flue gas temperature caused by excessive draft or excessive amount of air needed for combustion
Poor fuel combustionBad quality fuelUse fuel with the required parameters
Too little air supplied to the combustion processBlocked flap on the fan outlet – unlock the flap, change the position of the weights
Deposition of carbon on the exchanger, buildup of cementBad quality fuelUse fuel with the required parameters
Fuel with excessive moistureDry/replace the fuel, store fuel in and heated room.
Incorrect fuel combustionAdjust the settings of the electronic controller
Water getting out of the boilerThe so called “boiler sweating” is a natural phenomenon resulting from the temperature differences in the boilerAt boiler start-up and after each downtime the boiler should be “burned-in” i.e. fire it up to 70°C and maintain the temperature for several hours
Too low boiler temperature settingIncrease the temperature
Fuel with excessive moistureDry/replace the fuel
“Knocking/shooting” in the boilerAir pockets in the central heating system and the boiler, e.g. due to incorrect filling of the system and the boiler with water“Boiler burn-in”, i.e. maintaining the temperature of 70°C for an extended period, i.e. until the pockets of air are completely removed from the boiler. De-aeration of the system is done through radiator vents

Applicable to boilers with a feeder.

PROBLEMPOSSIBLE CAUSEREMEDY
Leaking gear oilNo sealing of gear gasketsReplacement of gear by technical support
Breaking of the safety componentFeeder jam – low quality fuel containing mechanical impurities: stones, pieces of metal, coal cobs, etc.Use fuel with adequate granulation and check for undesired components
Causes attributable to the fuel feeding systemRead the recommendations of the fuel feeder operating instructions
Smoke escapes from the fuel binIncorrect fuel feeding time settingAdjust the settings of the electronic controller
Contaminated cleanout openingsClean the openings
Poor flue draftMeasure the flue draft
Incorrect intake/exhaust ventilation in the boiler roomCheck the operation of supply and exhaust in the ventilation system
Check the operation of supply and exhaust in the ventilation systemMake up the shortage of fuel in the tank, minimum fill level – 25%
Damaged bin cover gasketReplace the gasket

We kindly inform you that, in the event of an unwarranted service call, the customer covers the cost of travel and the work of the service technician. To prevent this, please refer to the most common malfunctions of the boiler which result from improper installation or use of the boiler.